The amount of allowable or exposed glass is determined by type of glass being used and will vary depending on the hourly rating required.
Side light in fire rated wall.
Horizontal exits 2 1.
3 4.
Under nfpa 80 the side light frame and the glazing in the frame are considered part of the door assembly and are tested to nfpa 252 the fire test standard for doors.
Sidelites and transoms around a 20 minute fire door in a 1 hour exit require a 45 minute fire rating with hose stream.
Fire rated glazing marking door vision panel minimum side light transom assembly rating hr fire rated gla marking sid light transom p fire protection fire resistance fire protection f resis.
The testing and listing agencies have been testing and rating sidelites including the glazing component to the fire door test standard accordingly.
Fire rated glass is tested the same way that other fire rated materials are tested.
Table 600 note i.
Where fire protection ratings are required fire protection rated glazing shall be installed.
Where the fire separation distance is greater than 5 feet the exterior wall needs only be rated from the inside section 705 2.
When the code requires fire doors rated 1 hour or more then the sidelites and transoms around that door must be fire resistive and rated to the same standard as the wall itself e g 1 or 2 hour.
A wall is built in the side of a furnace.
Fire rated glass testing.
Fire rated systems are critical life safety components and need to be thoroughly reviewed in both the design and construction phases to ensure they meet code requirements.
The same requirement is in the standard building code published by the southern building code congress international inc.
The sidelites and transoms however must have a minimum fire protection rating of 45 minutes with hose stream.
In 1 hour fire partitions used as an exit corridors and in a 1 hour smoke barrier the code allows a 20 minute rated door with a vision panel tested without hose stream.
Transom frame sidelite frame assemblies are tested and listed for fire protection in accordance with ul10c and nfpa 252.
Property be rated for exposure to fire from both sides.
On fire rated transom and or sidelight frames and fire rated window frames steelcraft labeling procedures only control the o a width and or height of the frames based on wall condition.
Maximum size tested d h 90 or d h w 90 np 2 np d h w horizontal exits served by bridges between buildings 2.
These wall assembly files are used for planning and estimation purposes for many ul wall types such as fire rated wall assemblies.
Usg provides resources here for our ul wall assemblies for seamless integration into any construction project.